Power Factor Fundamentals & Correction Basics – Interview Questions and Answers (Part 1)

Power factor is a fundamental topic in electrical engineering interviews because it connects AC circuit theory with everyday industrial maintenance. Engineers and technicians must understand how reactive power affects current, transformer loading, cable losses and utility charges. A low power factor can restrict the usable capacity of an electrical installation even when its active power demand remains unchanged. Capacitor banks and automatic power factor correction panels help manage reactive power, but incorrect compensation may cause leading power factor or harmonic resonance. This first part explains essential formulas, practical operating principles and electricity billing concepts through thirteen interview questions and answers. Two interactive mock tests help you assess your knowledge before an interview.

13 Basic Power Factor Interview Q&A – Fundamentals

Jump to Question:
01

Q1. What is Power Factor (cos φ) in an AC electrical system, and what is its formula?

Answer: Power factor (PF) is the ratio of active power to apparent power in an AC electrical system. The general formula is PF = P/S = kW/kVA. For sinusoidal voltage and current, PF = cos φ, where φ is the phase angle between voltage and current. In a single-phase circuit, P = VI cos φ. In a balanced, sinusoidal three-phase circuit, P = √3 × VLL × IL × cos φ, in watts. For example, a load drawing 80 kW at 100 kVA has a power factor of 0.80. Power factor indicates how effectively the supply capacity is used, not the energy conversion efficiency of the equipment.
Practical Interview Tip: Use kW/kVA for true PF; use cos φ only when the sinusoidal assumption applies.

Read detailed article
02

Q2. What is the difference between Active Power (kW), Reactive Power (kVAR), and Apparent Power (kVA), and how does the Power Triangle relate them?

Answer: Active power (P, kW) is the average electrical power converted into useful work, heat or other energy. Reactive power (Q, kVAR) describes the oscillating energy exchange associated with inductive and capacitive fields under sinusoidal conditions. Apparent power (S, kVA) represents the voltage-current loading of equipment. In the sinusoidal power triangle, P is the horizontal side, Q is the vertical side and S is the hypotenuse. S = √(P² + Q²), PF = P/S = cos φ, and Q = P tan φ. A load of 80 kW and 60 kVAR therefore draws 100 kVA at 0.80 PF. The simple triangle does not capture harmonic distortion.
Practical Interview Tip: Explain the units and the right-angle relationship, not an arithmetic addition of kW and kVAR.

Read detailed article
03

Q3. What is the difference between Lagging Power Factor and Leading Power Factor?

Answer: Lagging power factor occurs when the fundamental current lags the fundamental voltage, as commonly observed with induction motors and transformers. Such inductive loads absorb positive reactive power under the conventional load sign convention. Leading power factor occurs when the fundamental current leads voltage, as with capacitive loads or an overcompensated capacitor bank. The net reactive power is then negative under the same convention. Both conditions can have the same numerical PF magnitude, but their electrical effects differ. Excessive leading compensation may cause voltage rise and other operating difficulties. For example, a lightly loaded plant with too many capacitor stages connected may shift from lagging to leading power factor.
Practical Interview Tip: Check both PF magnitude and the leading or lagging indication on the meter.

04

Q4. What is Unity Power Factor, and why do we set target PF to 0.98–0.99 instead of exact 1.00?

Answer: Unity power factor means active power equals apparent power: PF = P/S = 1.00. For sinusoidal waveforms, the phase angle is zero and net reactive power is zero. Industrial APFC systems often use a target near 0.98–0.99 lagging rather than trying to maintain exact unity. Load changes, discrete capacitor stages, switching delays and measurement tolerances can otherwise produce overcompensation or frequent switching. At 0.98 lagging, Q/P = tan(cos⁻¹ 0.98) ≈ 0.203. A slightly lagging target provides a practical operating margin, but it is not a universal setting. Select the target according to utility requirements, generator limitations, harmonic conditions and the approved system design.
Practical Interview Tip: A near-unity lagging setpoint is common; the final target must suit the actual installation.

Read detailed article
05

Q5. What are the main causes and disadvantages of a low power factor in industrial plants?

Answer: Common causes include lightly loaded induction motors, oversized transformers operating at low load, welding equipment, inductive lighting ballasts and insufficient reactive power compensation. Nonlinear electronic loads can also reduce true power factor through current distortion. For a balanced three-phase load at fixed voltage and active input power, IL = 1000P/(√3 × VLL × PF), with P in kW. A lower PF increases RMS current, causing higher I²R losses, greater voltage drop in many inductive networks and reduced spare capacity in transformers and cables. Utility demand charges or power factor penalties may also increase, depending on the tariff. Identify the cause before selecting corrective equipment.
Practical Interview Tip: Compare kW, kVAR, PF and harmonic readings under different plant loading conditions.

06

Q6. Why do induction motors operate at a very low lagging power factor (around 0.20) at no-load?

Answer: An induction motor needs magnetizing current to establish the rotating magnetic field in its air gap, even when no mechanical load is connected. At no-load, the active input mainly supplies core losses, friction, windage and winding losses. The reactive component of current remains significant while the active component is relatively small. Consequently, the phase angle is large and PF = P/S can be low, sometimes around 0.20 lagging. This value is illustrative, not universal; motor size, design, voltage and saturation affect the reading. As shaft load increases, the active current component generally increases and power factor usually improves toward its rated-load value.
Practical Interview Tip: Do not assume that a running motor has a high PF just because it is unloaded.

07

Q7. What is the difference between Power Factor and Load Factor?

Answer: Power factor describes the relationship between active and apparent power: PF = kW/kVA at a specified operating condition. Load factor describes how consistently electrical demand is used over a defined period. Load factor = average demand/maximum demand = energy (kWh)/(maximum demand (kW) × period (h)), when demand and energy use the same basis. For example, 1,200 kWh consumed over 24 hours with a 100 kW maximum demand gives a load factor of 0.50, or 50%. A plant can have excellent power factor but poor load factor if it operates intermittently. Improving one does not automatically improve the other.
Practical Interview Tip: State the measurement period when calculating load factor and the operating condition when quoting PF.

08

Q8. What is the difference between True Power Factor and Displacement Power Factor?

Answer: True power factor is the ratio of total active power to apparent power calculated using RMS quantities, PF = P/S. It accounts for waveform distortion as well as phase displacement. Displacement power factor (DPF) is cos φ₁, where φ₁ is the angle between fundamental voltage and current. With sinusoidal supply voltage and distorted current, PF = DPF × I₁/Irms = DPF/√(1 + THDi²), where THDi is expressed as a decimal. A variable frequency drive may therefore have near-unity DPF but lower true PF. Capacitors primarily correct displacement PF; harmonic current may require suitable filtering. The simplified formula does not apply unchanged when voltage is significantly distorted.
Practical Interview Tip: Check true PF, DPF and THD separately before recommending capacitors.

09

Q9. What is Power Factor Correction (PFC), and what are the different methods to improve it?

Answer: Power factor correction (PFC) improves the ratio of active to apparent power by reducing unnecessary reactive current and, where relevant, harmonic distortion. Common methods include fixed shunt capacitors for steady inductive loads, automatic stepped capacitor banks for varying loads, synchronous condensers and dynamic reactive power compensators. Active harmonic filters or suitable active front ends address distortion where appropriate. For a lagging sinusoidal load, the required capacitive compensation is Qc = P(tan φ₁ − tan φ₂), where P is in kW and Qc is in kVAR. The two angles correspond to the initial and target displacement power factors. Equipment selection requires a load and harmonic assessment.
Practical Interview Tip: Select the correction method according to load variation, harmonics and the electrical system design.

Read detailed article
10

Q10. How does a capacitor bank improve power factor, and why does line current decrease after PFC?

Answer: A shunt capacitor bank supplies leading reactive current that offsets part of the lagging reactive current demanded by inductive loads. The upstream source then supplies less net reactive power. At unchanged active power and voltage, apparent power S = P/PF decreases as PF improves. For a balanced three-phase system, IL = 1000P/(√3 × VLL × PF). For example, a 100 kW load at 400 V draws approximately 180.4 A at 0.80 PF and 147.3 A at 0.98 PF. This is an 18.4% current reduction upstream of the compensation point. The motor branch current itself need not decrease if the capacitor is connected at the main bus.
Practical Interview Tip: Always identify where the current is measured relative to the capacitor bank.

Read detailed article
11

Q11. Does power factor correction reduce actual energy consumption (kWh) in the electricity bill?

Answer: Power factor correction does not directly reduce the active energy needed by a motor, heater or production process delivering the same output. Active energy is E = ∫P dt, or E = P × t for constant power, expressed in kWh when power is in kW and time in hours. Compensation can reduce upstream current-dependent losses, particularly I²R losses in customer-owned cables and transformers. This may slightly reduce metered kWh if those losses occur downstream of the billing meter, after allowing for capacitor and associated equipment losses. Larger financial savings may arise from reduced kVA demand, apparent-energy charges or avoided PF penalties, depending on the tariff.
Practical Interview Tip: Never promise a fixed percentage reduction in kWh solely because PF has improved.

12

Q12. Why do electricity utilities impose penalties on low power factor and enforce kVAh billing?

Answer: Low power factor increases the current required to deliver a given active power, using more network capacity and increasing electrical losses. Some utilities therefore apply low-PF penalties, kVA demand charges or apparent-energy (kVAh) billing to encourage efficient use of the supply. For constant load and PF, kVAh = kWh/PF. For example, 800 kWh delivered at a constant 0.80 PF corresponds to 1,000 kVAh; at 0.98 PF, it corresponds to about 816.3 kVAh. For varying loads, apparent energy follows the meter’s specified integration method. Billing thresholds, leading reactive energy treatment and penalty rules differ by utility and customer category; not every utility uses kVAh billing.
Practical Interview Tip: Check the actual tariff and meter registers before estimating the financial benefit.

13

Q13. Why are transformers rated in kVA while motors are rated in kW?

Answer: A transformer is rated in kVA because its thermal loading depends mainly on applied voltage, frequency and current, rather than the connected load’s power factor. Core losses depend largely on voltage and frequency, while winding losses depend strongly on current. For a balanced three-phase transformer, S = √3 × VLL × IL/1000 kVA. A motor is normally rated by its mechanical shaft output in kW (or horsepower), which describes its useful work capacity. Its electrical input is Pin = Pout/η, where η is efficiency, and its apparent input is Sin = Pin/PF. For example, a 75 kW motor at 0.90 efficiency and 0.85 PF requires about 98.0 kVA input.
Practical Interview Tip: Distinguish motor shaft output from electrical input when sizing a supply transformer.

Test Your Knowledge Through Mock Test

Power Factor Fundamentals & Correction Basics · Two tests, 10 questions each. Choose a test below to begin.

Question 1 of 100 / 10 answered

Your answers stay on this page.

KEEP LEARNING WITH ELECTRICAL TOPIC

Learn Faster. Improve Your Electrical Skills.

WEBSITE • EMAIL UPDATES

New guides. Straight to your inbox.

Subscribe free. Get fresh website updates.

Have a question? Email info@electricaltopic.com

Videos in Hindi

Electrical Topic on YouTube

Watch practical electrical lessons from our YouTube channel.

Visit channel