Alternator Safety or protection
Types and their working functions.


Contents

  1. Safeties of Alternator

Safeties of Alternator:

The generating units, especially the larger ones, are relatively few in number and higher in individual cost than most other equipment’s. Therefore, it is desirable and necessary to provide Protection of Alternators to cover the wide range of faults which may occur in the modern generating plant.

  • Prime mover failure.
  • Failure of field.
  • Over current.
  • Over voltage.
  • Over speed.
  • Unbalance load.
  • Stator winding faults.
1 - Prime mover failure:

When input to the prime-mover fails, the alternator runs as a synchronous motor and draws some current from the supply system. This motoring conditions is known as “inverted running“.

Diesel engine driven alternators, when running inverted, draw a considerable amount of power from the supply system and it is a usual practice to provide Protection of Alternators against motoring in order to avoid damage due to possible mechanical seizure. This is achieved by applying reverse power relays to the alternators which *isolate the latter during their motoring action. It is essential that the reverse power relays have time-delay in operation in order to prevent inadvertent tripping during system disturbances caused by faulty synchronizing and phase swinging.

2 - Failure of field:

he chances of field failure of alternators are undoubtedly very rare. Even if it does occur, no immediate damage will be caused by permitting the alternator to run without a field for a short-period. It is sufficient to rely on the control room attendant to disconnect the faulty alternator manually from the system bus-bars. Therefore, it is a universal practice not to provide automatic protection against this contingency.

3 - Over current:

It occurs mainly due to partial breakdown of winding insulation or due to overload on the supply system. Overcurrent protection for alternators is considered unnecessary because of the following reasons :

4 - Over speed:

The chief cause of overspeed is the sudden loss of all or the major part of load on the alternator. Modern alternators are usually provided with mechanical centrifugal devices mounted on their driving shafts to trip the main valve of the prime-mover when a dangerous overspeed occurs.

5 - Over voltage:

The field excitation system of modern alternators is so designed that over-voltage conditions at normal running speeds cannot occur. However, over voltage in an alternator occurs when speed of the prime-mover increases due to sudden loss of the alternator load.

6 - Unbalance load:

Unbalanced loading means that there are different phase currents in the alternator. Unbalanced loading arises from faults to earth or faults between phases on the circuit external to the alternator. The unbalanced currents, if allowed to persist, may either severely burn the mechanical fixings of the rotor core or damage the field winding.

7 - Stator winding faults:

Unbalanced loading means that there are different phase currents in the alternator. Unbalanced loading arises from faults to earth or faults between phases on the circuit external to the alternator. The unbalanced currents, if allowed to persist, may either severely burn the mechanical fixings of the rotor core or damage the field winding.


Go back to index ↑

Electrical and Mechanical Job Interview Training.
Get boost in your job or get new opportunity

Technical e book is used for storing data in soft formate which may be pdf, ms word or others as availability.

Electrical E-book

(Get important knowledge about industrial electrical, building maintenance in E-book )

HT system, LT system, Transformer, Electrical panel, Motor and Starter, Circuit breakers, Protection relays, Measuring meters.
Read More ➠ Electrical E-Book

Interview is a physical verbal communication activity which is performed between job seekers and employers so that skilled person could be selected.

Technical Interview

( Electrical system, Diesel generator, BMS, AC, Chiller plant,
UPS, WTP, STP, ETP, Fire and safety.)

electrician, maintenance supervisor, AC operator, chiller plant operator, DG operator, BMS operator, Shift engineer, Maintenanceengineer, technical executive, sr. engineer, assistant facility manager,
Read More ➠Technical Interview

Learn Fast and Improve Your Skill in Electrical Field Basic and practical theory, repair and maintenance, protection and testing.

For any query :- write to us as below mentioned email ..

For official :-   admin@electricaltopic.com

For technical information :-   info@electricaltopic.com

For interview preparation :-  interview@electricaltopic.com
Subscribe for Get Latest Post Updates in Your Email Inbox
Join Free Email Service