Types and their working functions.


Contents

  1. Safeties of Alternator

Safeties of Alternator:

The generating units, especially the larger ones, are relatively few in number and higher in individual cost than most other equipment’s. Therefore, it is desirable and necessary to provide Protection of Alternators to cover the wide range of faults which may occur in the modern generating plant.

  • Prime mover failure.
  • Failure of field.
  • Over current.
  • Over voltage.
  • Over speed.
  • Unbalance load.
  • Stator winding faults.
1 - Prime mover failure:

When input to the prime-mover fails, the alternator runs as a synchronous motor and draws some current from the supply system. This motoring conditions is known as “inverted running“.

Diesel engine driven alternators, when running inverted, draw a considerable amount of power from the supply system and it is a usual practice to provide Protection of Alternators against motoring in order to avoid damage due to possible mechanical seizure. This is achieved by applying reverse power relays to the alternators which *isolate the latter during their motoring action. It is essential that the reverse power relays have time-delay in operation in order to prevent inadvertent tripping during system disturbances caused by faulty synchronizing and phase swinging.

2 - Failure of field:

Loss of excitation can cause a grid-connected generator to draw reactive power and can lead to heating or instability. Loss-of-field protection is one function used in generator protection schemes. Its selection and settings depend on the machine and system studies.

3 - Over current:

Generator overcurrent protection can provide backup for external faults or respond to other overcurrent conditions, depending on the relay and scheme. The generator’s fault-current behavior and protection coordination determine how the function is applied.

4 - Over speed of Alternator:

The chief cause of overspeed is the sudden loss of all or the major part of load on the alternator. Modern alternators are usually provided with mechanical centrifugal devices mounted on their driving shafts to trip the main valve of the prime-mover when a dangerous overspeed occurs.

5 - Over voltage:

Overvoltage can result from overspeed, load rejection or excitation-control problems. The alternator protection scheme may include overvoltage and overexcitation functions selected for the application.

6 - Unbalance load:

Unbalanced phase currents produce negative-sequence current, which can heat the rotor. Compare the generator’s negative-sequence capability with the protection scheme and expected loading.

7 - Stator winding faults:

Stator faults include phase-to-phase and phase-to-earth winding faults. Generator differential and stator earth-fault protection are examples of schemes selected for the generator size, winding connections and earthing arrangement.


Go back to index ↑

KEEP LEARNING WITH ELECTRICAL TOPIC

Learn Faster. Improve Your Electrical Skills.

Read practical guides on our website and subscribe to our Hindi technical YouTube channel. Learn testing, maintenance, troubleshooting and interview skills.

WEBSITE • EMAIL UPDATES

New guides. Straight to your inbox.

Subscribe free. Get fresh website updates.

Have a question? Email info@electricaltopic.com

Videos in Hindi

Electrical Topic on YouTube

Watch practical electrical lessons from our YouTube channel.

Visit channel