Air Circuit Breaker (ACB) Types: Fixed, Draw-out, EDO & MDO
Types of Air Circuit Breaker (ACB)
Select an LT air circuit breaker by pole count, rated current, mounting, short-circuit performance, operating method and trip unit. Modern LT ACBs use arc chutes to split and cool the arc in atmospheric air. This guide focuses on practical LT panel selection under IEC 60947-2.
A- Pole Types (3P and 4P)
3-Pole (3P) ACB
A 3P ACB switches the three phase conductors. Use it for a three-wire feeder or where the approved earthing and supply design calls for a continuous, unswitched neutral.
4-Pole (4P) ACB
A 4P ACB switches the three phases and neutral. Use a switched neutral when the approved earthing design requires neutral isolation, such as some diesel generator (DG) to transformer changeovers with separately earthed source neutrals. Confirm the specified neutral rating and switching sequence. The protective earth conductor stays connected.
B- Rated Current
Across common product families, ACB ratings run from 630 A to 6300 A. Some families also offer a 400 A lower-frame option where ACB and MCCB ratings overlap. The available steps vary by make. Check the frame size, sensor or rating plug, where fitted, and the permitted long-time pickup setting against the feeder load and the derated conductor capacity.
- 630 A
- 800 A
- 1000 A
- 1250 A
- 1600 A
- 2000 A
- 2500 A
- 3200 A
- 4000 A
- 5000 A
- 6300 A
C- Fixed and Draw-out ACBs
Fixed ACB
A fixed ACB bolts to the panel with permanent primary connections. It has no draw-out cradle. Removal requires authorised isolation and disconnection under the equipment procedure.
Draw-out ACB
The breaker moves in a compatible cradle for testing and maintenance. Check the position indicator and the manufacturer's instructions for these positions:
- Service (Connected): Primary and control connections are engaged for normal operation.
- Test: Primary connections are separated. Control connections are usually available for approved functional checks.
- Isolated (Disconnected): Primary connections are separated and the control connections are typically disengaged. Check the cradle position indicator and the manufacturer’s connection diagram. Confirm the isolation boundaries and absence of voltage under the site’s approved isolation procedure before work.
D- Breaking Capacity and Withstand Ratings
Match the breaker's short-circuit ratings to the prospective fault current and the actual operating voltage. Letter codes such as N, H, S and L are manufacturer-specific and can vary by product range. Use the exact datasheet for the selected frame, voltage and performance code. The table gives product-specific examples.
| Example code | Icu at 415 V AC |
|---|---|
| H1 | 42 kA |
| H2 | 50 kA |
| H3 | 66 kA |
| L1 | 150 kA |
Example ratings are from the Schneider Electric MasterPacT MTZ1 user guide. Under IEC 60947-2, check three distinct ratings:
- Icu (ultimate short-circuit breaking capacity): The prospective short-circuit current the breaker can interrupt under the standard ultimate duty at the stated voltage.
- Ics (service short-circuit breaking capacity): The current the breaker can interrupt under the service duty and remain suitable for continued service under the standard test criteria. Catalogues often state it as a percentage of Icu.
- Icw (rated short-time withstand current): The current the closed breaker can withstand for a declared duration, often 1 s. Check both the kA value and duration when coordinating short-time delays.
E- EDO and MDO Operation
1- Electrically Operated Draw-Out (EDO)
An EDO ACB typically has a motor to charge the closing spring, a closing coil for electrical close commands and a shunt trip coil for electrical open commands. Remote closing and tripping require a compatible control circuit, correct auxiliary supply and the approved interlocks.
2- Manually Operated Draw-Out (MDO)
In the basic MDO configuration, the operator charges the closing spring by hand and uses two push buttons for local ON and OFF operation. Optional accessories depend on the model. With a standard draw-out cradle, both EDO and MDO are racked manually using the manufacturer’s handle and interlocks. A motor used to charge the spring does not drive the racking mechanism. Powered racking requires a separate compatible accessory or mechanism.
F- Protection and Trip Units
1- Thermal-Magnetic
A thermal element responds to sustained overload, while a magnetic element trips rapidly at high short-circuit current. This design is commonly encountered in MCCBs. Its overload response is inverse-time. Confirm the trip curve for the installed device if this release is offered.
2- Solid-State
A solid-state release uses current sensors and electronic circuitry to detect overcurrent and apply pickup and delay settings. On older panels, compare the installed release model and dial settings with its time-current curve before testing.
3- Microprocessor-Based LSIG
A digital trip unit can provide long-time overload (L), short-time short-circuit (S), instantaneous short-circuit (I) and ground-fault (G) protection. Confirm which functions are fitted. Compare the pickup values and delays with the approved coordination study before commissioning.
Video: Types of air circuit breakers
Watch this related lesson in Hindi from Electrical Topic.
The YouTube player loads when you choose Play. Watch on YouTube.