Skip to content
Electrical TopicPractical guides. Stronger skills.Learn in Hindi

AMF Panel for DG Set: Working, Wiring Diagram & Parts


AMF- auto mains failure panel.

Contents

  1. What Is an AMF Panel?
  2. AMF Panel Wiring Diagram
  3. AMF Panel Working Principle
  4. Main Components of an AMF Panel

1 - What Is an AMF Panel?

An Automatic Mains Failure (AMF) panel monitors the utility supply and controls transfer to a standby generator when the utility is unavailable. It can also manage return to the utility and generator cooldown.

2 - AMF Panel Wiring Diagram

AMF panel wiring  diagram,single line diagram and working principle.

Power path: The utility (EB/mains) incomer and the DG incomer feed the common load bus through an automatic transfer switch (ATS) or an approved interlocked pair of contactors or breakers. In open-transition operation, the connected source opens before the alternate source closes. The installation's earthing design determines whether the neutral is switched.

Control path: The AMF controller senses mains voltage and generator voltage and frequency, then issues a start/stop request to the DG controller through the specified relay or interface. Breaker or contactor auxiliary contacts report the actual open/closed position. If the commanded position and feedback disagree, the controller follows the approved alarm and inhibit logic.

Use the diagram to identify the power and control paths. For site work, use the approved panel schematic and confirm sensing inputs, control supply and position feedback in the authorised test mode.

3 - AMF Panel Working Principle

In an open-transition system, the AMF controller confirms mains failure, starts the generator and checks generator voltage and frequency before transfer. The changeover equipment opens one source before closing the other. When utility supply is healthy for the configured return delay, the load transfers back and the generator cools down before stopping.

AMF Sequence & Typical Timer Settings

The values below are illustrative controller settings. Confirm the approved settings for the DG, ATS, load and site requirements before commissioning.

Example settings for an open-transition mains-to-DG sequence
StageIllustrative settingWhat happens
Mains fail delay5 sConfirms the mains fault persists before starting the DG.
DG cranking and attempts10 s crank, 10 s rest, up to 3 attempts as an exampleStops cranking when the engine starts. If all permitted attempts fail, the controller raises a fail-to-start alarm and inhibits transfer.
Warm-up and transfer delay5 s example transfer delay after source acceptance, plus any required engine warm-upConfirms DG voltage and frequency are acceptable and the load can transfer once the opening feedback and interlocks permit it.
Mains return stabilization delay60–300 s example settingsWaits for a sustained healthy mains supply before opening the DG source and transferring the load back.
DG cooldown delay60 s example settingKeeps the DG running unloaded after retransfer, then removes the run request if the approved sequence permits it.

Timer examples are based on the Deep Sea Electronics DSE72/7300 operating manual and Cummins transfer switch guidance. The actual crank count and rest interval must follow the engine and starter specifications.

4 - Main Components of an AMF Panel

1 - Metering Section

Measuring meters: Voltmeters and ammeters show voltage and current. A multifunction meter can also display frequency, power and energy. Select digital or analogue instruments to suit the panel specification and check their configured CT or VT ratios where applicable.

Indicators: Different types of indicators are used with distinct colors. Typical indications include R, Y and B phase availability, DG running and source connected. Read the lamps against their legends and the panel drawing.

Push buttons: Local controls may include DG Start, DG Stop and Emergency Stop, as specified by the panel design.

Selector switches: A panel may have current or voltage selectors and an Auto/Manual selector. Verify the selected mode before judging an automatic sequence.

2 - AMF Controller & ATS Section

AMF controller: The controller monitors source conditions, issues the DG start/stop request, runs the timers and checks breaker or contactor position feedback.

ATS / changeover system: The power switching assembly may use a purpose-built ATS, a pair of interlocked 4-pole contactors, motorized MCCBs, or electrically operated draw-out (EDO) ACBs with suitable ratings. Four poles are used where the approved earthing design requires neutral switching. Mechanical and electrical interlocking prevent both sources from closing together in an open-transition system. Check the interlock and position feedback using the approved functional test.

3 - Static Battery Charger

The charger maintains the DG starter battery, typically a 12 V or 24 V set as specified. Float mode maintains charge during standby. Boost mode supports recharging after discharge where the battery and charger specifications permit it. Check charger status and the battery manufacturer's settings before troubleshooting a slow crank.

4 - Protection & Sensing Relays

Phase-failure and under/overvoltage functions decide whether the mains or DG supply is acceptable. Earth-fault protection measures residual or earth current and acts through the approved protection scheme. Some functions are integrated in the AMF controller or breaker release, while others use separate relays. Verify the sensing inputs, settings and trip indications against the coordination schedule.


Go back to index ↑


KEEP LEARNING WITH ELECTRICAL TOPIC

Learn Faster. Improve Your Electrical Skills.

WEBSITE • EMAIL UPDATES

New guides. Straight to your inbox.

Subscribe free. Get fresh website updates.

Have a question? Email info@electricaltopic.com

Videos in Hindi

Electrical Topic on YouTube

Watch practical electrical lessons from our YouTube channel.

Visit channel