AMF Panel for DG Set: Working, Wiring Diagram & Parts
1 - What Is an AMF Panel?
An Automatic Mains Failure (AMF) panel monitors the utility supply and controls transfer to a standby generator when the utility is unavailable. It can also manage return to the utility and generator cooldown.
2 - AMF Panel Wiring Diagram

Power path: The utility (EB/mains) incomer and the DG incomer feed the common load bus through an automatic transfer switch (ATS) or an approved interlocked pair of contactors or breakers. In open-transition operation, the connected source opens before the alternate source closes. The installation's earthing design determines whether the neutral is switched.
Control path: The AMF controller senses mains voltage and generator voltage and frequency, then issues a start/stop request to the DG controller through the specified relay or interface. Breaker or contactor auxiliary contacts report the actual open/closed position. If the commanded position and feedback disagree, the controller follows the approved alarm and inhibit logic.
Use the diagram to identify the power and control paths. For site work, use the approved panel schematic and confirm sensing inputs, control supply and position feedback in the authorised test mode.
3 - AMF Panel Working Principle
In an open-transition system, the AMF controller confirms mains failure, starts the generator and checks generator voltage and frequency before transfer. The changeover equipment opens one source before closing the other. When utility supply is healthy for the configured return delay, the load transfers back and the generator cools down before stopping.
AMF Sequence & Typical Timer Settings
The values below are illustrative controller settings. Confirm the approved settings for the DG, ATS, load and site requirements before commissioning.
| Stage | Illustrative setting | What happens |
|---|---|---|
| Mains fail delay | 5 s | Confirms the mains fault persists before starting the DG. |
| DG cranking and attempts | 10 s crank, 10 s rest, up to 3 attempts as an example | Stops cranking when the engine starts. If all permitted attempts fail, the controller raises a fail-to-start alarm and inhibits transfer. |
| Warm-up and transfer delay | 5 s example transfer delay after source acceptance, plus any required engine warm-up | Confirms DG voltage and frequency are acceptable and the load can transfer once the opening feedback and interlocks permit it. |
| Mains return stabilization delay | 60–300 s example settings | Waits for a sustained healthy mains supply before opening the DG source and transferring the load back. |
| DG cooldown delay | 60 s example setting | Keeps the DG running unloaded after retransfer, then removes the run request if the approved sequence permits it. |
Timer examples are based on the Deep Sea Electronics DSE72/7300 operating manual and Cummins transfer switch guidance. The actual crank count and rest interval must follow the engine and starter specifications.
4 - Main Components of an AMF Panel
1 - Metering Section
Measuring meters: Voltmeters and ammeters show voltage and current. A multifunction meter can also display frequency, power and energy. Select digital or analogue instruments to suit the panel specification and check their configured CT or VT ratios where applicable.
Indicators: Different types of indicators are used with distinct colors. Typical indications include R, Y and B phase availability, DG running and source connected. Read the lamps against their legends and the panel drawing.
Push buttons: Local controls may include DG Start, DG Stop and Emergency Stop, as specified by the panel design.
Selector switches: A panel may have current or voltage selectors and an Auto/Manual selector. Verify the selected mode before judging an automatic sequence.
2 - AMF Controller & ATS Section
AMF controller: The controller monitors source conditions, issues the DG start/stop request, runs the timers and checks breaker or contactor position feedback.
ATS / changeover system: The power switching assembly may use a purpose-built ATS, a pair of interlocked 4-pole contactors, motorized MCCBs, or electrically operated draw-out (EDO) ACBs with suitable ratings. Four poles are used where the approved earthing design requires neutral switching. Mechanical and electrical interlocking prevent both sources from closing together in an open-transition system. Check the interlock and position feedback using the approved functional test.
3 - Static Battery Charger
The charger maintains the DG starter battery, typically a 12 V or 24 V set as specified. Float mode maintains charge during standby. Boost mode supports recharging after discharge where the battery and charger specifications permit it. Check charger status and the battery manufacturer's settings before troubleshooting a slow crank.
4 - Protection & Sensing Relays
Phase-failure and under/overvoltage functions decide whether the mains or DG supply is acceptable. Earth-fault protection measures residual or earth current and acts through the approved protection scheme. Some functions are integrated in the AMF controller or breaker release, while others use separate relays. Verify the sensing inputs, settings and trip indications against the coordination schedule.



