Single-Phase Motor Multimeter Test: Winding Resistance
Prepare the motor for testing
Have qualified personnel isolate the motor from all sources and verify absence of voltage under the site procedure. Identify drive connections, terminal links and any capacitors from the motor drawing. Follow the approved instructions for disconnection and discharge before testing.
Identify motor windings
Use the motor drawing to identify the main and auxiliary windings. Some motors share a common terminal or have an internal start device. Compare winding readings with the manufacturer’s data for that motor design.
Measure winding resistance
Use a suitable low-resistance measurement method where the expected readings are close to the meter or lead resistance. Compare equivalent readings and the expected values at the measured winding temperature.
Continuity and open winding checks
An open indication across an identified winding may indicate an interrupted winding or connection. Verify the terminal identification and meter setup. A continuity beep shows that a conducting path exists within the meter’s threshold.
Screen for unintended continuity
Use the motor drawing to identify paths that should be separate. A low-resistance reading between such paths calls for investigation. An insulation resistance tester is required for a specified insulation test.