AC Motor Practical Interview Questions – Electrical Testing & Measurements

10 AC Motor Interview Q&A – Practical Part 1

Read short answers about electrical testing & measurements, then try two mock tests.

Jump to Question:
01

Q1. How do you measure current in all three phases and assess current unbalance?

Answer: Use a suitable current instrument to compare the three phase currents under stable load at approved measurement points. Current unbalance is 100 times the maximum departure from the three-reading average divided by that average, with limits set by the manufacturer or site. Investigate supply voltage, connections and loading if the trend rises.

Read detailed article
02

Q2. How do you perform a motor insulation-resistance (IR) test and assess the result?

Answer: An insulation-resistance test assesses winding insulation against earth using a DC insulation tester on a safely isolated motor. For some low-voltage motors ABB specifies 500 or 1000 V DC and a 100 MΩ reference corrected to 25°C, subject to the model manual. Have authorised staff isolate connected electronics, discharge the winding and trend temperature-corrected results.

Read detailed article
03

Q3. What causes motor vibration? How do you measure it and check limits?

Answer: Motor vibration can come from imbalance, misalignment, looseness, bearing damage or the driven machine. Measure vibration at repeatable bearing points, typically as velocity in mm/s RMS, and select the applicable ISO 20816 or manufacturer limit for the installation. Compare readings at similar speed and load and investigate the direction showing the largest change.

Read detailed article
04

Q4. How do you use thermography to check motor temperature and hot terminal boxes?

Answer: Thermography helps compare apparent temperatures at accessible motor surfaces and electrical connections while the equipment is under representative load. Record temperature in °C, load current, emissivity and comparable phase temperatures, because shiny surfaces and reflections can distort readings. Use approved viewing arrangements and schedule an isolated inspection when one connection consistently runs hotter.

Read detailed article
05

Q5. How do you check motor earthing and investigate leakage to the motor body?

Answer: Check that the motor frame has a sound protective-earth connection and investigate insulation damage if earth leakage is suspected. Protective bonding is assessed by continuity or low-resistance measurement against the installation design, while insulation resistance is a separate reading in MΩ. Have authorised staff isolate the equipment and check glands, cable damage and moisture before reinstatement.

Read detailed article
06

Q6. How do you measure and compare the three-phase motor winding resistances?

Answer: Measure the three winding resistances on an isolated motor using a suitable low-resistance instrument and the maker’s connection procedure. Compare readings in ohms at the same temperature and use four-wire measurement where lead resistance is significant. If one reading differs, recheck the test connections and compare with recorded values before suspecting winding damage.

Read detailed article
07

Q7. What is the polarization index (PI) test, and when is it useful?

Answer: The polarization index shows how insulation resistance changes during a timed DC insulation test. PI equals the ten-minute reading divided by the one-minute reading, and IEEE 43 gives 2.0 as a common minimum for class B and higher where applicable. Compare the result with the maker’s criteria and the existing temperature-corrected trend.

Read detailed article
08

Q8. How do you measure starting or inrush current safely?

Answer: Starting current is captured with an instrument that has a suitable inrush function at an approved measurement point. Record peak or RMS inrush as specified by the meter, along with acceleration time and steady current, because peak and RMS values are different. Have authorised staff compare the trace with the motor and starter data.

Read detailed article
09

Q9. How do you measure motor supply-voltage unbalance and trend it in the logbook?

Answer: Measure all three line-to-line voltages under comparable operating conditions and calculate the largest deviation from the average. NEMA voltage unbalance is that deviation divided by average voltage times 100, with 1% a common reference for rated operation. Log the readings and load, then investigate recurring differences before increasing motor load.

Read detailed article
10

Q10. How do you check motor winding continuity with a multimeter during maintenance?

Answer: A multimeter continuity check can identify an open winding path on a safely isolated motor with the connections identified. A closed path should show finite resistance, while an open path normally displays OL, but a continuity beep cannot detect many shorted-turn faults. Compare phase readings and request the appropriate winding test if a fault remains suspected.

Read detailed article

Test Your Knowledge Through Mock Test

Motor Practical – Part 1 · Two tests, 10 questions each. Choose a test below to begin.

Question 1 of 100 / 10 answered

Your answers stay on this page.

KEEP LEARNING WITH ELECTRICAL TOPIC

Learn Faster. Improve Your Electrical Skills.

WEBSITE • EMAIL UPDATES

New guides. Straight to your inbox.

Subscribe free. Get fresh website updates.

Have a question? Email info@electricaltopic.com

Videos in Hindi

Electrical Topic on YouTube

Watch practical electrical lessons from our YouTube channel.

Visit channel