Transformer Basic Interview Questions – Transformer Losses and Efficiency

20 Transformer Interview Q&A – Basic Part 3

Learn about transformer losses, efficiency and voltage regulation with 20 short answers and two mock tests.

41

Q41. What is transformer efficiency and how is it calculated?

Answer: Transformer efficiency is the useful output power divided by input power at the stated load and power factor. If output is 100 kW and total loss is 2 kW, efficiency is 100/102 × 100, or about 98.0%. Use the same load and temperature basis when comparing vendor data or site test results.

Read detailed article
42

Q42. What is transformer voltage regulation?

Answer: Voltage regulation describes the change in secondary voltage between no-load and specified load at constant primary voltage and tap. A common definition is (Vno-load − Vload)/Vload × 100, with the result depending on load current and power factor. Check primary voltage, tap and load before blaming regulation for a low LV reading.

Read detailed article
43

Q43. What is hysteresis loss?

Answer: Hysteresis loss is energy used to reverse magnetic domains in core steel during each AC cycle. It increases with frequency and flux density, and grain-oriented steel helps reduce it when the flux follows the preferred grain direction. Compare excitation and no-load watts at the rated volts per hertz if core loss appears unusually high.

Read detailed article
44

Q44. What is eddy-current loss?

Answer: Eddy-current loss occurs when changing flux induces circulating currents in conductive core material, causing heating. For comparable sinusoidal conditions, classical eddy loss varies roughly with lamination thickness squared, frequency squared and flux density squared. After core repair, compare no-load watts with factory data and investigate signs of damaged lamination insulation under approved inspection.

Read detailed article
45

Q45. At what condition does a transformer achieve maximum efficiency?

Answer: Maximum efficiency occurs at the load where variable load losses equal approximately constant no-load losses, for fixed voltage and power factor. In a simple model, the optimum load fraction is √(Pcore/Pload,rated), since variable losses scale roughly with current squared. Use factory no-load and corrected load-loss data to estimate where the unit operates most efficiently.

Read detailed article
46

Q46. What is all-day efficiency of a distribution transformer?

Answer: All-day efficiency measures energy delivered over a full day divided by energy drawn during the same period. Over 24 hours, kWh losses include nearly continuous no-load loss and load loss that varies with the demand profile. Use load interval data and the test-sheet loss figures to compare transformers serving an intermittent distribution load.

Read detailed article
47

Q47. What causes the normal humming sound of a transformer under AC excitation?

Answer: Normal transformer hum largely comes from magnetostriction, where the core steel changes shape slightly as its magnetisation varies. On a 50 Hz supply, a prominent component is often near 100 Hz because the effect repeats twice per cycle. Compare sound with the normal baseline and investigate sudden increases, abnormal vibration or cooling equipment noise.

Read detailed article
48

Q48. Why is the power factor typically low when a transformer operates at no load?

Answer: At no load, a transformer draws a small no-load current (typically 2% to 5% of full-load current), which is mostly reactive magnetising current to establish core flux and only a tiny active component to supply core losses. Because reactive power dominates over active power, the no-load power factor is very low—typically around 0.10 to 0.25 lagging.

Read detailed article
49

Q49. What is transformer leakage flux and how does it affect leakage reactance and regulation?

Answer: Leakage flux links one winding more strongly than the other and therefore contributes to transformer leakage reactance. In the equivalent circuit, leakage reactance combines with winding resistance to form percentage impedance and affects voltage regulation, especially with lagging loads. Compare the specified impedance, load power factor and tap before diagnosing an LV voltage drop.

Read detailed article
50

Q50. What is copper loss in a transformer?

Answer: Copper loss is the resistive heating produced by current in transformer windings, including windings made from aluminium in common usage. Basic winding loss is I²R, so doubling current at the same resistance increases this part of loss four times. Compare loading and temperature and account for additional stray load losses in factory results.

Read detailed article
51

Q51. What is core or iron loss in a transformer?

Answer: Core or iron loss is the power absorbed by the energized core, even when the transformer supplies no external load. Its main components are hysteresis and eddy-current loss, and IEC 60076 no-load measurements specify voltage and frequency conditions. Check supply voltage, frequency and waveform when comparing measured no-load watts with the factory record.

Read detailed article
52

Q52. Why can a transformer be more efficient than a comparable rotating electrical machine?

Answer: A transformer can achieve high efficiency because its power transfer is static and avoids shaft friction and windage. Its principal losses are no-load loss and load loss, which are evaluated under specified IEC 60076 test conditions, with auxiliary cooling demand considered separately as applicable. Compare equipment at matched duty and output before drawing conclusions.

Read detailed article
53

Q53. What does the vector group Dyn11 mean?

Answer: Dyn11 means the high-voltage winding is delta and the low-voltage winding is star with its neutral terminal brought out. Clock number 11 indicates a 30-degree displacement, with LV leading HV under the usual clock convention. Verify actual terminal relationships and phase sequence before connecting parallel transformers or approving differential relay compensation settings.

Read detailed article
54

Q54. What are OLTC and RTCC, and how are their functions different?

Answer: The OLTC changes the active winding tap while the transformer remains loaded, and the RTCC provides remote indications and control commands. A scheme may use 1.25% tap steps and voltage feedback, but the approved nameplate and settings determine actual values. Compare local and remote tap indications if the secondary voltage fails to respond.

Read detailed article
55

Q55. What are the basic functions of Buchholz relay, OTI, WTI and ONAN/ONAF cooling?

Answer: A Buchholz relay protects oil-filled conservator transformers against internal faults (alarm on slow gas accumulation, trip on sudden oil surge). OTI and WTI monitor top-oil and winding hot-spot temperatures (typical alarm/trip settings: OTI 85°C/95°C, WTI 95°C/105°C). ONAN uses natural oil and air cooling, while ONAF adds forced cooling fans to handle higher loads.

Read detailed article
56

Q56. What are the main conditions for parallel operation of transformers?

Answer: For safe parallel operation, transformers must have the same voltage ratio (same tap setting), same vector group/phase shift, same polarity and phase sequence, and nearly equal percentage impedance (%Z, typically within ±10%). Mismatched voltage ratios cause circulating current, while mismatched %Z causes unequal load sharing.

Read detailed article
57

Q57. What does percentage impedance mean on a transformer nameplate?

Answer: Percentage impedance is the voltage percentage needed to circulate rated current during a specified short-circuit test. For a 5% transformer on a stiff source, a simplified terminal fault estimate is about 20 times rated current, neglecting upstream impedance. Use the approved short-circuit study rather than this estimate for breaker duty or protection settings.

Read detailed article
58

Q58. How do star-delta and delta-star three-phase transformer connections differ?

Answer: In Star–Delta (Yd), the primary is Star and secondary is Delta, commonly used in step-down substations at the end of transmission lines. In Delta–Star (Dyn11), the primary is Delta (circulating 3rd harmonics) and secondary is Star with an accessible neutral—making it standard for 11 kV/433 V distribution transformers supplying 3-phase 4-wire loads (415 V line-to-line and 240 V line-to-neutral).

Read detailed article
59

Q59. Why is a tap changer provided on a power or distribution transformer?

Answer: A tap changer varies the effective turns on the HV winding (typically in steps of 1.25% or 2.5%, e.g., +5% to −15%) to keep secondary output voltage stable when incoming supply voltage fluctuates. An OCTC (Off-Circuit Tap Changer) must only be operated after complete de-energization, whereas an OLTC (On-Load Tap Changer) changes taps automatically or manually while the transformer remains under load.

Read detailed article
60

Q60. What is transformer polarity and why is it verified before parallel operation?

Answer: Polarity indicates the relative instantaneous voltage direction of HV and LV terminals—either subtractive (standard for power transformers) or additive. Verifying polarity before parallel operation is critical because connecting two transformers with opposite polarity creates a dead short circuit across the windings even if their RMS voltages match.

Read detailed article

Test Your Knowledge Through Mock Test

Basic Part 3 · Two tests, 10 questions each. Choose a test below to begin.

Question 1 of 100 / 10 answered

Your answers stay on this page.

KEEP LEARNING WITH ELECTRICAL TOPIC

Learn Faster. Improve Your Electrical Skills.

WEBSITE • EMAIL UPDATES

New guides. Straight to your inbox.

Subscribe free. Get fresh website updates.

Have a question? Email info@electricaltopic.com

Videos in Hindi

Electrical Topic on YouTube

Watch practical electrical lessons from our YouTube channel.

Visit channel