01

Q1. What is a transformer?

Answer: A transformer is a static electrical machine that transfers AC power between circuits and can change the voltage level. IS 2026 and IEC 60076 cover power transformers, with typical distribution nameplates showing 11 kV/433 V at 50 Hz. Before selecting a unit, verify the voltage ratio, frequency, kVA rating and required winding connection.

Read detailed article
02

Q2. How does a transformer work?

Answer: A transformer works by creating alternating magnetic flux in its core, which induces voltage in another winding. At 50 Hz, the induced voltage is proportional to winding turns for the same linked flux, according to E = 4.44fNΦmax for sinusoidal flux. During commissioning, compare the measured turns ratio and tap position with the nameplate.

Read detailed article
03

Q3. How are winding turns and voltage related?

Answer: The winding with more turns develops a higher voltage when both windings link the same alternating flux. Ideally, V₁/V₂ = N₁/N₂ for individual winding phase voltages, so 1000 turns and 100 turns give a ratio of 10:1. For three-phase units, account for star or delta connections before comparing the measured line-voltage ratio.

Read detailed article
04

Q4. What are the main parts of an oil transformer?

Answer: An oil transformer consists of a laminated CRGO core and HV/LV windings inside a steel tank filled with insulating oil, along with HV/LV bushings, cooling radiators, a conservator tank, silica-gel breather, Buchholz relay, pressure relief valve (PRV), OTI/WTI gauges, and a tap changer (OLTC/OCTC).

Read detailed article
05

Q5. What is mutual induction?

Answer: Mutual induction occurs when changing flux produced by one winding links another winding and induces voltage in it. Faraday’s law gives the induced voltage as e = −N dΦ/dt, with the minus sign describing opposition to the flux change. If output voltage is wrong, verify the supply, winding connections and tap indication against the drawing.

Read detailed article
06

Q6. Why does a transformer use AC?

Answer: A transformer needs changing flux to sustain an induced secondary voltage, which an AC supply provides continuously. At a given applied voltage and tap, reducing frequency below the nameplate value, such as 50 Hz, increases volts per hertz and can saturate the core. Check the supply waveform and frequency before connecting the unit.

Read detailed article
07

Q7. What happens if DC is given to a normal transformer?

Answer: A transformer cannot work on DC because steady DC produces constant magnetic flux, so no EMF is induced in the secondary winding. Since frequency is zero (XL = 0), there is no inductive reactance—only very low winding resistance limits the current, causing heavy current to flow and burn out the primary winding.

Read detailed article
08

Q8. What is the EMF formula of a transformer?

Answer: The EMF equation relates induced voltage to frequency, winding turns and maximum flux in the core. For sinusoidal flux, the RMS value is E = 4.44fNΦmax, with frequency in hertz and flux in webers. When comparing readings, use winding phase voltage and the actual tap turns rather than mixing line and phase values.

Read detailed article
09

Q9. How does Faraday’s law work in a transformer?

Answer: Faraday’s law explains that any winding linked by changing magnetic flux develops an induced voltage. In a transformer, e = −N dΦ/dt applies to each winding, so windings sharing the same flux develop voltage in proportion to turns. Use the expected ratio and polarity to check winding identification during an authorised commissioning test.

Read detailed article
10

Q10. Does a transformer change frequency?

Answer: A normal power transformer changes voltage and current while retaining the frequency of the applied AC supply. If the primary receives 50 Hz, the transformer secondary fundamental is also 50 Hz, although waveform distortion may be present. Check both frequency readings with a suitable instrument if a downstream load reports a frequency problem.

Read detailed article
11

Q11. How does power pass from primary to secondary?

Answer: Alternating flux links the windings, and when the secondary is loaded, the primary draws additional current to support the transferred power. For an ideal transformer, V₁I₁ = V₂I₂ on a phase basis, while a real unit also draws magnetising current and supplies losses. Compare input and output loading using matched readings and winding connections.

Read detailed article
12

Q12. Why are bushings used in a transformer?

Answer: Bushings carry energized winding connections through an earthed tank or enclosure while insulating the conductor from it. IEC 60137 ratings include voltage class and current, and a bushing used on an 11 kV system must suit the equipment insulation level. Inspect for contamination, cracks and leakage from an approved position before escalating any defect.

Read detailed article
13

Q13. Why is a transformer core made from thin sheets?

Answer: Thin insulated core sheets reduce eddy-current loss by limiting large circulating current paths through the steel. Grain-oriented electrical steel laminations may be around 0.27–0.35 mm thick, depending on grade, design and loss targets. If no-load loss increases after repair, have the core assembly, insulation and test conditions checked against the factory baseline.

Read detailed article
14

Q14. Why is transformer oil used?

Answer: Transformer mineral oil serves two main purposes: electrical insulation between live windings and the earthed tank, and cooling by transferring heat from the core/windings to the radiators. In service, oil health is monitored through tests like BDV (typically above 30–40 kV for in-service distribution transformers) and moisture content per IEC 60422 / IS 1866.

Read detailed article
15

Q15. What is a conservator tank?

Answer: A conservator provides expansion space so the main tank can remain full as the oil volume changes with temperature. A conservator gauge is assessed against its specified temperature reference, and some designs use a bladder to separate oil from air. Compare oil level with temperature and look for leakage if the level falls unexpectedly.

Read detailed article
16

Q16. What does a silica-gel breather do?

Answer: A silica-gel breather absorbs moisture from incoming air when the transformer oil cools and contracts. Fresh blue silica gel turns pink when saturated (orange turns green in eco-gel) and should be replaced or reactivated once 50–70% changes colour. The bottom oil-seal cup prevents continuous contact between outside air and the silica gel.

Read detailed article
17

Q17. What is the difference between primary and secondary winding?

Answer: The primary winding receives electrical input from the source, while the secondary winding delivers electrical output to the connected load. In an 11 kV/433 V step-down installation supplied on the HV side, the HV winding is primary and the LV winding is secondary. Verify the actual source side from the approved single-line diagram.

Read detailed article
18

Q18. Why is a magnetic core used?

Answer: The magnetic core provides a low-reluctance path that links the windings and reduces the magnetising effort needed for a given flux. For a sinusoidal supply, Φmax = E/(4.44fN), so excessive voltage per hertz can drive the steel into saturation. Check excitation current and supply frequency if the unit draws unusually high no-load current.

Read detailed article
19

Q19. Why is CRGO steel used in transformer cores?

Answer: CRGO steel is used because its magnetic properties along the rolling direction help reduce magnetising current and core loss. Insulated laminations, commonly available in grades around 0.27 mm or 0.30 mm, also reduce eddy-current circulation. After core work, compare no-load loss and excitation measurements with factory records taken under matching test conditions.

Read detailed article
20

Q20. Why are copper or aluminium used for windings?

Answer: Copper and aluminium are used because both conduct winding current well and can be formed into suitable conductors. Copper has lower resistivity, so an aluminium design generally uses a larger conductor cross-section for comparable resistance, subject to thermal design. Check winding material and termination compatibility before specifying repair, replacement or joint hardware.

Read detailed article

Test Your Knowledge Through Mock Test

Transformer Basic – Part 1 · Two tests, 10 questions each. Choose a test below to begin.

Question 1 of 100 / 10 answered

Your answers stay on this page.

KEEP LEARNING WITH ELECTRICAL TOPIC

Learn Faster. Improve Your Electrical Skills.

WEBSITE • EMAIL UPDATES

New guides. Straight to your inbox.

Subscribe free. Get fresh website updates.

Have a question? Email info@electricaltopic.com

Videos in Hindi

Electrical Topic on YouTube

Watch practical electrical lessons from our YouTube channel.

Visit channel