Cable Size Calculator — Voltage Drop & Entered Ampacity

Estimate a conductor-size candidate from your chosen voltage-drop limit, with an optional check against your own manufacturer ampacity table.

ELECTRICAL TOPICCable Size Calculator

Your result

CABLE PLANNINGREADY
—Enter values below and press Calculate.
RESULT DISPLAYA + m → mm²

Input values

ENTER YOUR EQUIPMENT DATA
Across the load for single phase; line-to-line for three phase.
A project input; not a universal statutory limit.

Formula and worked example

ΔV = k × I × L × ρ / A; Amin = k × I × L × ρ / ΔVallowed. k = 2 for single-phase/DC, √3 for balanced three-phase. L is one-way metres. ρ = 0.0237 (Cu) or 0.0376 (Al) Ω·mm²/m for the normal-service approximation. Optional thermal check: Iz × derating ≥ I.

Worked example

At 230 V, 20 A, 30 m one-way, copper and a chosen 3% limit: Amin = 4.1217 mm². The next displayed standard area is 6 mm², giving 4.74 V / 2.0609% drop in this resistive model. Thermal capacity has not been established by that result.

Using this tool

Enter the actual equipment and project values. The Use example button loads an illustrative case. Calculation happens in your browser; no Python, API key or account is required. Use the result details to see the inputs and scope, copy the result, download CSV or print.

यह पहले voltage-drop के हिसाब से न्यूनतम area निकालता है। केवल mm² दिखने का अर्थ पूरी cable selection या safety approval नहीं है। Ampacity के लिए सही manufacturer table और correction factors दें।

Advertisement

Common questions

Does the displayed size mean the cable is safe to install?

It is a planning candidate within the stated model. Ampacity, protective-device coordination, fault withstand, earth/neutral sizing and actual installation conditions require separate verification.

Why is cable reactance not used?

This first model uses PF = 1 and X = 0 with a normal-service resistance approximation. For appreciable reactance, poor power factor or large conductors, use applicable datasheet R/X and a full installation calculation.

What happens if no size meets my table?

The display reports no candidate. It does not extrapolate ampacity or invent a larger approved conductor.

Related practical guides

Advertisement

Other calculators

Formula references and model scope

Formula review: 2 November 2026. Examples are illustrative. Enter project-specific data; a planning result does not certify an installation or equipment selection.

KEEP LEARNING WITH ELECTRICAL TOPIC

Learn Faster. Improve Your Electrical Skills.

Read practical guides on our website and subscribe to our Hindi technical YouTube channel. Learn testing, maintenance, troubleshooting and interview skills.

WEBSITE • EMAIL UPDATES

New guides. Straight to your inbox.

Subscribe free. Get fresh website updates.

Have a question? Email info@electricaltopic.com

Videos in Hindi

Electrical Topic on YouTube

Watch practical electrical lessons from our YouTube channel.

Visit channel