Transformer Practical Interview Questions – OTI WTI and Cooling

15 Transformer Interview Q&A – Practical Part 5

Review transformer temperature indicators, alarms and cooling checks in short answers and two mock tests.

61

Q61. What does OTI stand for?

Answer: OTI stands for oil temperature indicator and commonly displays the temperature at a specified top-oil sensing point. The temperature is shown in degrees Celsius, and alarm or trip contacts are set to the approved transformer schedule for that instrument. Compare the reading with load, ambient temperature and cooling status before deciding whether it is abnormal.

Read detailed article
62

Q62. What does WTI stand for?

Answer: WTI stands for winding temperature indicator, which usually represents an estimated winding temperature on a conventional oil transformer. A thermal-image WTI combines an oil-sensing element with a CT-fed heater to simulate winding rise, while some designs use direct sensing. Check the specified CT ratio, settings and instrument type before judging whether the indication is credible.

Read detailed article
63

Q63. Why do we monitor OTI and WTI?

Answer: OTI and WTI are monitored to detect excessive thermal stress and check whether the cooling system is responding to load. Compare temperatures in degrees Celsius with the approved fan-start, alarm and trip settings, which differ between transformer designs. Log load, ambient temperature and cooling stage together so a high reading can be interpreted correctly.

Read detailed article
64

Q64. What can cause a high OTI reading?

Answer: High OTI can result from high loading, hot ambient conditions, poor radiator performance, low oil level or faulty indication. Compare top-oil rise above ambient at similar kVA and cooling state, using the applicable IEC 60076 loading guidance and manufacturer limits. Check fan status and trend direction from a safe position before escalating an abnormal rise.

Read detailed article
65

Q65. What can cause a high WTI reading?

Answer: High WTI can indicate high winding loading, poor cooling, phase imbalance or a problem with the temperature indication circuit. A conventional thermal-image WTI depends on oil temperature and a CT-derived heating input, so current and CT setup affect its reading. Compare phase load and OTI trends and have authorised staff verify the indication if they disagree.

Read detailed article
66

Q66. What should we check when a cooling fan does not run?

Answer: When a fan does not run, determine whether it has a valid start demand and whether its supply or protection has operated. Check the approved stage temperature in degrees Celsius, selector mode, contactor status and motor protection indication against the control drawing. Have authorised staff investigate a failed stage without bypassing the protection or fan guards.

Read detailed article
67

Q67. What is the purpose of a transformer radiator?

Answer: A transformer radiator transfers heat from circulating oil to surrounding air through a larger cooling surface. In an ONAN design, both oil and air circulate naturally, while an ONAF design uses fans to increase airflow over the surface. Verify radiator valve position and airflow from approved checks if a section behaves differently from its peers.

Read detailed article
68

Q68. What does an oil pump do in a transformer?

Answer: An oil pump forces oil through the cooling circuit on transformer designs that require forced circulation. IEC cooling codes such as OFAF identify forced oil and forced air, and the actual flow permissives and alarm settings are model-specific. Check pump status, flow indication and cooler staging against the operating schedule if temperature rises unexpectedly.

Read detailed article
69

Q69. What is ONAN cooling?

Answer: ONAN means Oil Natural Air Natural, so transformer oil circulates by natural convection and heat passes to naturally moving external air. The transformer nameplate gives its ONAN kVA rating, which may differ from a fan-assisted rating on the same unit. Confirm radiator availability and the applicable rating before accepting a sustained load in this mode.

Read detailed article
70

Q70. What is ONAF cooling?

Answer: ONAF means Oil Natural Air Forced, with natural oil circulation and fans increasing heat removal from the cooling surfaces. The applicable ONAF kVA rating and required fan stages are stated in manufacturer documentation and may be higher than ONAN ratings. If fans are unavailable, review permissible loading against the approved operating instructions.

Read detailed article
71

Q71. Why are cooling fans started in stages?

Answer: Fans are staged so cooling capacity increases as transformer temperature rises without running all fans at light load. Each stage has approved start and stop temperatures in degrees Celsius, with separation between them to limit frequent cycling. Compare stage indications with the actual temperature trend and report a fan group that fails to operate when demanded.

Read detailed article
72

Q72. How do we verify OTI and WTI alarm settings?

Answer: Verify OTI and WTI contacts against the approved cooling and protection settings, including the correct alarm or trip destination. Record specified and measured operating and reset temperatures in degrees Celsius using the manufacturer’s approved simulation or calibration procedure. Have authorised staff confirm control logic and restore all test arrangements before returning the transformer to service.

Read detailed article
73

Q73. Why clean radiator surfaces?

Answer: Clean radiator surfaces allow air to pass freely and improve heat transfer from the oil to the surroundings. Dust or debris can reduce both natural convection in ONAN and fan airflow in ONAF, raising temperature at similar load. Use the approved safe cleaning method and review temperature trends after the work to confirm the effect.

Read detailed article
74

Q74. What is a cooling equipment inspection?

Answer: A cooling inspection checks radiators, fans, pumps where fitted, control indications, airflow paths and visible oil leakage. Record the active cooling code or stage, operating temperatures and flow or fan status against the required configuration. Report failed components and verify the permitted loading if the transformer cannot achieve its normal cooling duty.

Read detailed article
75

Q75. What should we do if temperature rises fast?

Answer: A fast temperature rise calls for immediate reporting and assessment against the transformer’s approved operating instructions. Check OTI and WTI trends in degrees Celsius together with load, ambient conditions and fan or pump availability, while observing site safety boundaries. Have the authorised operator decide whether load reduction or a shutdown is required.

Read detailed article

Test Your Knowledge Through Mock Test

Practical Part 5 · Two tests, 10 questions each. Choose a test below to begin.

Question 1 of 100 / 10 answered

Your answers stay on this page.

KEEP LEARNING WITH ELECTRICAL TOPIC

Learn Faster. Improve Your Electrical Skills.

WEBSITE • EMAIL UPDATES

New guides. Straight to your inbox.

Subscribe free. Get fresh website updates.

Have a question? Email info@electricaltopic.com

Videos in Hindi

Electrical Topic on YouTube

Watch practical electrical lessons from our YouTube channel.

Visit channel