ANSI Device Codes List, Differential (87) & Earth Fault Relay Interview Q&A

15 ANSI Code, Differential & Earth Fault Q&A – Core Functions

Learn common ANSI device codes, breaker control contacts, differential and earth fault protection, and other important relay functions. The practical examples are for learning, not approved site settings. Then try the two mock tests.

Jump to Question:
01

Q1. What are ANSI device numbers and which standard (IEEE C37.2) defines them?

Answer: ANSI device numbers are short codes used to identify protection and control functions on electrical drawings. IEEE C37.2 defines these function numbers and related naming conventions. For example, 50 means instantaneous overcurrent, 51 means time overcurrent, 52 means an AC circuit breaker, 87 means differential protection, and 86 means lockout. Other common codes are 21 for distance, 27 for undervoltage, 32 for directional power, 59 for overvoltage, 67 for directional overcurrent and 81 for frequency. On an 11 kV panel, one numerical relay may contain several of these functions. The number identifies the function, not the relay model. Always check the drawing legend and relay manual because suffixes can vary between manufacturers and projects.

Read detailed article
02

Q2. What do ANSI 52, 52a, and 52b auxiliary contacts mean on a control wiring diagram?

Answer: ANSI 52 identifies an AC circuit breaker. The 52a and 52b contacts are auxiliary contacts linked to the breaker mechanism. In normal service, 52a is closed when the main breaker is closed and opens when the breaker opens. The 52b contact normally works in the opposite way. A trip circuit often uses 52a to cut off trip coil current after the breaker opens. The 52b contact may be used in closing circuits, position indication or trip circuit supervision. For example, if an 11 kV VCB shows the wrong position on the control panel, check the auxiliary contact status, terminal wiring and mechanism under an approved isolation procedure. The actual circuit drawing must always be followed.

Read detailed article
03

Q3. What is a master trip / lockout relay (ANSI 86) and how does it differ from ANSI 94 tripping relay?

Answer: An ANSI 86 lockout relay receives trip signals from serious protection functions, such as transformer differential or restricted earth fault. It can trip several breakers and block their closing circuits. The lockout condition remains active until an authorised reset is performed. Reset may be manual or electrical, depending on the design. An ANSI 94 tripping relay normally transfers or repeats a trip command to a breaker or other equipment without maintaining a separate lockout state. Some 94 schemes also provide trip-free logic. For example, a transformer 87T operation may start an 86 relay to trip both HV and LV breakers. Before resetting an 86 relay, identify the fault, review the records and obtain the required clearance. Never bypass the closing block.

Read detailed article
04

Q4. What is the function of a Trip Circuit Supervision relay (74TCS)?

Answer: A trip circuit supervision relay continuously checks whether the breaker trip circuit is healthy. It can detect problems such as loss of DC control supply, an open trip coil or broken wiring, depending on the supervision circuit. Many schemes use a small monitoring current and the breaker auxiliary contacts 52a and 52b to supervise the circuit in both open and closed positions. The monitoring current is limited so that it does not operate the trip coil. A 74TCS alarm means the breaker may not trip when required; it does not prove that the main breaker mechanism is faulty. Engineers should check the DC supply, fuses, wiring and supervision circuit safely. The base ANSI 74 code means alarm relay; TCS is an application label.

Read detailed article
05

Q5. What is the difference between 50N/51N (residual earth fault) and 50G/51G (ground earth fault via CBCT)?

Answer: In many relay schemes, 50N and 51N use the residual current from three phase CTs. The relay measures the vector sum of the phase currents, which is normally close to zero in a healthy three-wire circuit. A ground fault can produce residual current. A 50G or 51G element may instead receive current from a core balance current transformer (CBCT) or a separate ground CT. A CBCT measures the combined current of the live conductors passing through it and can provide sensitive earth fault detection. In both groups, 50 is instantaneous and 51 is time overcurrent. The N and G labels are not universal. Check the relay manual, CT wiring and earthing arrangement before deciding which element is used.

Read detailed article
06

Q6. What is the difference between 51N (non-directional earth fault) and 67N (directional earth fault)?

Answer: A 51N relay detects earth fault current above its pickup setting and operates after the selected time characteristic. It does not normally identify the direction of the fault current. A 67N relay adds a direction check before allowing earth fault operation. It commonly compares residual current with a suitable reference signal, such as residual voltage, using a configured directional characteristic. The reference method depends on the relay and system earthing. On a simple radial feeder with one supply source, 51N may be sufficient. In a ring network or a system with parallel supplies, fault current may flow from either direction, so 67N can help isolate the correct feeder. Check CT and VT polarity, direction settings and test results during commissioning.

Read detailed article
07

Q7. What is the working principle of a differential relay (ANSI 87)?

Answer: A differential relay compares the currents entering and leaving a protected zone. CTs are installed at the zone boundaries and their signals are referred to a common basis. During normal load or an external fault, the corrected currents should balance. During an internal fault, this balance changes and a differential operating current appears. When the operating and restraint conditions are met, the relay issues a trip command. For example, transformer differential protection compares currents on the HV and LV sides after allowing for CT ratios and the transformer vector group. Wrong CT polarity, ratio settings or CT saturation can cause an incorrect differential current. Engineers should check the relay measurements, event records and approved test results before returning equipment to service.

Read detailed article
08

Q8. Why is a biased (percentage) differential relay preferred over a simple differential relay?

Answer: A simple differential relay operates when the difference between the measured currents exceeds a fixed threshold. During a heavy external fault, CT errors or unequal CT saturation can create a false difference even when the protected equipment is healthy. A biased differential relay uses both operating current and restraint current. As the restraint current increases, the relay generally requires more differential current to operate. This improves stability during heavy through-fault currents while keeping good sensitivity to internal faults at lower current levels. Transformer relays may also use separate inrush detection and restraint features. On site, engineers check the bias slopes, CT data and internal and external fault test results. Bias improves protection stability but does not replace correct CT selection and wiring.

Read detailed article
09

Q9. What is the difference between 87T, 87G, 87B, 87L, and 87M differential relays?

Answer: All these functions use the differential protection principle, but they protect different equipment. 87T protects a transformer and normally includes ratio and phase shift compensation. 87G is commonly used for generator differential protection. 87B protects a busbar by comparing the currents of its connected circuits. 87L protects a line or cable by comparing current measurements at its ends, usually through a communication channel. 87M protects a motor, often using CTs at the ends of its stator windings where suitable connections are available. Each scheme has different CT, restraint and trip requirements. For example, a busbar fault may require several breakers to open together. Suffixes may vary, so confirm the actual function in the equipment protection schedule and relay manual.

Read detailed article
10

Q10. What is the difference between Restricted Earth Fault (64REF / 64R) and 87T transformer differential protection?

Answer: Restricted Earth Fault (REF) provides sensitive protection for earth faults within a defined winding zone, commonly on a grounded star winding of a transformer. It compares the residual current from the phase CTs with the current measured by the neutral CT. It can detect some earth faults near the neutral that may produce too little differential current for 87T to operate. Transformer differential protection (87T) covers the transformer zone between its CTs and detects many internal phase and earth faults. It is not a replacement for sensitive REF protection. REF does not normally protect faults outside its own CT boundaries. Check the CT polarity, neutral earthing and protection zone on the approved drawing. REF may also be called 87N or 87REF.

Read detailed article
11

Q11. When and why is a directional overcurrent relay (ANSI 67) required?

Answer: An ANSI 67 relay combines overcurrent detection with a direction check. It allows the overcurrent element to operate for faults in a configured direction, normally using current and a suitable voltage reference. This is useful when fault current can flow from more than one source. Examples include ring feeders, parallel transformers and networks with generators connected at different points. A non-directional relay may detect a fault on a neighbouring circuit and trip an otherwise healthy feeder. Directional protection helps engineers achieve selective fault clearing when correctly coordinated. On an 11 kV ring panel, forward and reverse directions must be defined using the approved single-line diagram. Verify CT and VT polarity, the directional characteristic and coordination study before commissioning.

Read detailed article
12

Q12. What is the working principle of a distance relay (ANSI 21)?

Answer: A distance relay measures the apparent impedance between its location and a fault using voltage and current signals. In simple terms, impedance is related to voltage divided by current. For a suitable transmission line fault loop, the measured impedance is related to the electrical distance to the fault. The relay checks whether this impedance falls inside a configured operating characteristic. Several protection zones are commonly used, with different reaches and operating times for main and backup protection. A distance relay does not directly measure physical distance in kilometres. Fault resistance, remote source contribution, CT or VT errors and line conditions can affect its measurement. Engineers must use the approved line impedance data and protection study when checking settings or test results.

Read detailed article
13

Q13. Why is a reverse power relay (ANSI 32) used in generators and DG sets?

Answer: A reverse power relay monitors the direction of active power flow. A generator normally supplies active power to the electrical system. If its diesel engine or other prime mover loses mechanical power while the generator remains connected to a live bus, the generator may start taking active power from that bus and behave like a motor. This can damage or stress the prime mover. The reverse power function can trip the generator breaker after the configured reverse power level and time delay are reached. It is especially useful for DG sets operating in parallel. ANSI 32 is a directional power function, not only a reverse power function. Check the power sign, CT and VT connections, and manufacturer-approved settings during testing.

Read detailed article
14

Q14. Where are 27 (undervoltage), 59 (overvoltage), and 81 (under/over frequency) relays used?

Answer: ANSI 27 detects voltage below a configured limit, while ANSI 59 detects voltage above a configured limit. These functions are used in generator panels, motor feeders, substations and utility supply monitoring. ANSI 81 detects abnormal frequency; 81U and 81O commonly identify underfrequency and overfrequency functions. For example, a DG set with a sudden load change may experience a temporary frequency dip. A correctly configured frequency relay can issue an alarm, initiate load shedding or trip equipment if the abnormal condition continues. Voltage and frequency functions often include time delays to avoid unnecessary operation during permitted disturbances. Engineers should check nominal voltage, nominal frequency, VT ratio and the approved protection requirements rather than copying settings from another panel.

Read detailed article
15

Q15. What is a Buchholz relay and why is it not listed as a standard ANSI electrical code?

Answer: A Buchholz relay is a gas and oil flow operated protection device fitted in the pipe between the main tank and conservator of a suitable oil-filled transformer. Gas from a developing internal fault may collect in the relay and operate an alarm contact. A severe internal fault can cause a rapid oil surge and operate the trip contact. It is not used in the same way on dry-type transformers or sealed units without a suitable conservator pipe. Although Buchholz is the name of a mechanical protection device rather than a separate base ANSI function number, it is often identified by device 63 or a project-specific suffix such as 63B. Check the drawing legend and investigate any alarm or trip before re-energising.

Read detailed article

Test Your Knowledge Through Mock Test

ANSI Codes, Differential & Earth Fault · Two tests, 10 questions each. Choose a test below to begin.

Question 1 of 100 / 10 answered

Your answers stay on this page.

KEEP LEARNING WITH ELECTRICAL TOPIC

Learn Faster. Improve Your Electrical Skills.

WEBSITE • EMAIL UPDATES

New guides. Straight to your inbox.

Subscribe free. Get fresh website updates.

Have a question? Email info@electricaltopic.com

Videos in Hindi

Electrical Topic on YouTube

Watch practical electrical lessons from our YouTube channel.

Visit channel